Distribution Network Equipment
Home Distribution Network Equipment
HF-863

Terminal of Distribution Station

Product Introduction

Comply to DL/T721、GB/T13729

product details
ItemUnitValue 
Environment temperature-40 to +70
Relative humidity %5 to 95
AC voltage input nominal valueV220 or 100(specify when ordering)
AC current input nominal valueA

5 or 1(specify when ordering)

Frequency

Hz50
Overload capacity

1.2In continuous operation; 20In allows 1 second

1.2Un continuous operation;5Un allows 1 second

Power outage working timeHour>8
Whole machine power consumptionVA≤20
Collection accuracy 

AC voltage、current:0.5级

DC voltage、current:0.5级

power、power factor:level 1

frequency:≤±0.01Hz

SOE resolutionms≤2
Output contact capacity
DC24V/16A or DC48V/10A
Electromagnetic compatibility performance
level IV
Communication protocol
Support IEC60870-5-101/104
Wiring method
Terminal or aviation plug